Configuring a Modbus Plus Network in Modsoft with Peer Cop
870USE10110 July 2004 227
3 Type the value 1 in the LEN column of the SPECIFIC INPUT field, indicating that the
device at address 2 will transmit 1 word of data (or 16 bits). Then push <Enter>.
Result: The cursor is now on BIN (binary) the TYPE column.
4 Push <Enter>.
Result: A popup menu appears. You can choose between leaving the data type as
binary or changing it to BCD.
Step Action
Utility
GoToNode
AddNode OnError Quit
F1
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
Timeout : 240 ms Total Links: Link Id:1
PEER COP
On Error : HOLD USED 13 OF 1366 WORDS
REFERENCE LEN TYPE INDEXMODE
F2
Timeout
Access to Node : 2
TO ALL NODES ON LINK
GLOBAL OUTPUT -
DelNode
SPECIFIC INPUT 300016-300016 1 BIN
SPECIFIC OUTPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
Utility GoToNode AddNode OnError Quit
F1
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
Timeout : 240 ms Total Links: Link Id:1
PEER COP
On Error : HOLD USED 13 OF 1366 WORDS
REFERENCE LEN TYPE INDEXMODE
F2
Timeout
Access to Node : 2
TO ALL NODES ON LINK
GLOBAL OUTPUT -
DelNode
SPECIFIC INPUT 300016-300016 1 BIN
SPECIFIC OUTPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
BIN
BCD