I/O Mapping an I/O Bus Network
208
870USE10110 July 2004
Supporting an I/O Map for an I/O Bus Network with Modsoft for Momentum
Components
Introduction The 171 CCS 760 00 and 171 CCC 760 10 processor adapters have an I/O bus
communication port that enables them to control and communicate with network
slave I/O.
If you are using I/O bus to control network I/O, you need to write an I/O map in your
configuration. This section describes the configuration parameters required to
support an I/O map for I/O bus.
I/O Map
Reserved Words
By default, 512 words are reserved for I/O mapping. This may or may not be the
appropriate memory allocation to support your I/O bus network. A rule of thumb for
roughly estimating the number of words required for I/O mapping is:
16 words for overhead
10 words/module on the network (including both the local and the network I/O)
The idea behind adjusting the memory size is to allow you to completely I/O map
your network while preserving as much user memory as possible for your application
program.
Required
Settings
Be sure that the following parameters are set on the Configuration Overview screen.
Next Step Once you are sure that your Configuration Overview parameters are set properly,
you can access a second I/O Map screen for the I/OBus network (see p. 209).
Parameter Setting
Processor type
12.0 for a 171 CCS 760 00 processor adapter
18.0 for a 171 CCC 760 10 processor adapter
Number of segments 2
I/O map reserved words Enough to support your I/O map